Release Notes for INCOM QUCM Application: ----------------------------------------- 14May09 - Check to see if not on BIM or AEM for DT1150 on read 302. 01Dec08 - Removed 303 poll. 24Nov08 - Added 3CA Energy display to Energy Summary web page. 27Feb08 - Modbus/TCP Socket 3 was called twice instead of using socket 4. 29Aug07 - Added Temperature Buffer, Transformwer Voltages Buffer, Flags to MPCV. 29Jun07 - Fixed Modbus/TCP socket 4 to not use socket 3. Added program information. New compiler. NOTE: QLOAD must be upgraded to version 18Jun2007 or later. 24Jun05 - Added Modbus RTU intercharacter timeout setting. Added Port 2 Modbus/PNIM timeout setting to web page. Fixed Port 2 Device Type statistics display. Fixed initialization problem that possibly locked Port 2 in PNIM or RTU mode. 23Jun05 - Added support for Modbus opcode 06 single register write. 22Jun05 - Fixed Power Factor on IQDP. Fixed Currents on IQDP. 21Jun05 - Fixed Power and Reactive Power on IQDP from MW to KW. Fixed display on web page of data for IQDP. 27May05 - Fixed PNIM/RTU dual mode to toggle properly. 26Apr05 - Fixed MP3000 polling so it isn't always "Device Missmatch". 08Apr05 - Fixed display of MP3000 as Energy Sentinal. Fixed program halt on IQ DP read. 06Apr05 - Added MP3000. Fixed IQ Data Plus with software rev = 4 always missmatch. 28Sep04 - Added Digitrip 520MC. 17Aug04 - Fixed clobbered data on summary index 198 and 199. 30Jul04 - Added THD buffer read for IQ Analyzer. 14May04 - Added Energy rollover protection for IQDPII. Fixed port number on Edit web page. Fixed 30A energy disply detection. 19Nov03 - Fixed the Error 404 HTTP reply. 30Oct03 - The new 50 devices are now moved to 133 through 182 to allow for the possible PNIM and RTU devices on Port 2 (101 - 132). 28Oct03 - New QUCM firmware and compiler. Make sure that you load the new firmware. Increased the number of devices from 100 to 150. Installed a new flash storage mechanism. The program recognizes both the old and new format but only saves as the new. 16Apr03 - Added check for AEM Com Rev > 6 for DT 810 and 910 pass through. 31Mar03 - Added check for IP Address 10.10.10.10 restore from flash. 24Feb03 - Fixed default QUCM port = P1. Fixed an offline problem on Expanded Energy Buffer N=8 for energy units of M. It worked fine for K. 18Feb03 - Added summery index 198 with non-inverted/swapped bits for the Addressable relays. bit 0 is input 1 and bit 1 is input 2. Added web page setup for changing the QUCM's IP Address. 04Feb03 - Added actual setting of Frequency, CT and PT secondary on IQAnalyzer 23Jan03 - Added Demand Phase Current, Demand Power, Peak Demand Current, and Peak Demand Power for IQ Analyzer. Added 32-bit Modbus integer values for Energy Readings. 13Dec02 - Added input, output, and analog input to IQ Analyzer. 01Oct02 - Completely changed the entire system to allow INCOM devices on both QUCM serial ports. Also allow for up to 4 separate INCOM/TCP sockets. The system now allows for up to 100 devices. Added support for the IQ500. The web server has been completely reworked to make it easier to use on dial-up. NOTE: This version will not run on a QUCM-SE. You must upgrade the firmware on the QUCM-LE to the included version or it will not work. NOTE: The general summary on Index 99 has been moved to index 199. NOTE: If connecting to an EMINT, you must only use a single socket for all devices connected to that EMINT. Otherwise, split the EPONI slaves across multiple sockets for best performance. 19Jul02 - Added a summary of general status of each device on Modbus/TCP Index 99. Registers 1 through 7 are a bitmap of the online devices. Register 10 is the pointer to the slavedata value and it is writeable but defaults 38. The device data starts on register 11. Also increased the timeout on PNIM/PLOGIC/RTU port 2 to 5 seconds. 03Jul02 - Fixed name/data ram overlap. Added CTS open detection on Port 1. Fixed potential WRITELOCK contention. 02Jul02 - Changed max number of INCOM devices to 56. Force PNIM and PLOGIC to duplex full multidrop false. 26Jun02 - Added support for EPONI. Enter the IP Address of the EPONI in the device add web page. If the device is connected to the QUCM's serial port through a MINT then leave the IP Adddres at 0.0.0.0. PowerNet users may also connect to the EPONI meters bye using the QUCM as an EMINT in thier system. Simply use the Destination Index of each EPONI device as the device address in PowerNet. Increas the reply timeout to 4000mS in PowerNet. Added the three Input Counters to the IQ Analyzer. IQ Com Rev must be 7 or higher. New firmware to fix possible stack corruption problem. 21Dec01 - Fixed scale factors on PT Ratios for V > 32K. 08Oct01 - Found an open powerflag on Digitrip Optim read the caused I1=0. 14Sep01 - Added fast status read of all devices between each device data poll. Forced currents = 0 on 810 on main network if marked open. Fixed 3CA energy read of 810 and 910 on AEM. 07Sep01 - Force register 6 = 0 on Addressable Relay before masking bits. 06Sep01 - Removed the display of Frequency and Reactive Power from Digitrips. Fixed Digitrip Power Factor through AEM. 23Aug01 - Added Ditrip Optim to setup selection list. 22Aug01 - Added additional telent debug information. 21Aug01 - Set app2 debug false to auto-restart on errors. Fixed powerflag incorrectly dividing Power Factor on direct Digitrips so the result was always 0. 13Aug01 - Breaker Open/Closed is now determined by the Ditrip Flags buffer instead of the fast status. 08Aug01 - Fixed false Digitrip "High Load" instead of "OPEN" indication on AEM rev > 6. Fixed Digitrip trip download on AEM rev > 6. Added setup and storage of device type. The device in the field must now match the device assigned to the QUCM or the QUCM will mark the device offline. Fixed Ditrip 810 name display. App2 debug false. 02Jul01 - Added support for IQ200 and Addressable Relay. Added Modbus/TCP device 255 support for reading/writeing the local QUCM registers. Changed the "ALARM" dislplay on the web server to only show Digitrip "High Load" alarm. 26Jun01 - Added support for Digitrip MV and Digitrip 3000. Changed the display for tripped and alarms. 20Jun01 - Added support for Digitrip Optim. Added Previous/Next meter links to device pages. Changed device tables to conserve space. Added support for 3CA Energy readings in Digitrips. 30Apr01 - Fixed support for AEM rev > 6. 20Apr01 - Added support for Digitrip 810 and 910 on main network. 05Oct00 - Fixed a sign problem with floating point conversions. Mostly noted with Power Factor. 27Sep00 - Fixed a lockup of port 1 if p2mode <> 1. 22Sep00 - Added support for port 2 to be INCOM Slave, PNIM/RTU, PNIM only, RTU only, PLOGIC, and RTU Slave. Fixed the value out of bounds error on PNIM mode. 13Sep00 - Fixed display of IQ1000. Added 30 second socket timeouts. 31Aug00 - Added support for Energy Sentinal, Power Sentinal, IQ1000, IQ1000II, and Universal RTD. Added the FTP server to uload/download the flash paramter blocks. Fixed PNIM error replies and size problems. 29Jun00 - Added full support for PT and CT ratios to fix scaling problems for IQData/Generator, IQDP, IQDP2, IQDP4000, IQAnalyzer. Added statistical counters for PNIM/RTU mode. 07Jun00 - Added support for Energy for IQDP4000 and IQ Analyzer. Added statistical counters for timeouts, BCH errors, etc. Added a retry for Incom port 1 polls. 19May00 - Added support for port 2 connected to IMPACC PC with a straight serial connection. Configure IMPACC for a MINT II connection set for 19.2K, N,8,1 No Ack and a timeout of 1500. Removed support for connection from a second MINT on port 2. Fixed a problem with the scaling factors. Fixed a restore from flash startup problem. 24Mar00 - Replaced the telnet server with a web server in APP2. Removed the SY/MAX/Modbus slave serial driver for port 2. All SMS access is done through Modbus/TCP Ethernet. This application is no longer supported in the non-Ethernet versions of the QUCM. Added support for Port 2 to be a PNIM/Modbus RTU Master. The PNIM and/or RTU slaves are connected to Port 2 and all should be set to the same baud rate and parity. Their addresses should be set within the range of 1 to 32 inclusive. These devices are accessed via Modbus/TCP using Destination Index values of 101 though 132. Added support to connect another IMPACC Master to QUCM Port 2. Set port 2 to INCOM Slave mode and connect the Master directly using RS232 or through another MINT II. If using a MINT, turn off the ACK/NAK. 19200 baud is recommended for both QUCM serial ports. All settings are now in FLASH for permanent non-volatile security. 14Jul99 - Fixed a problem with learning IQ Analyzers. Added support for the new TCP stack in the QUCM. Requires QUCM firmware REV 13JUL99 or later. 25Jun99 - Added Modbus/TCP and Telnet Server. Allows up to 4 Modbus/TCP connections at the same time. Listens on Port 502. Telnet server allows 1 connection and listens on TELNET port 23. The user should change the Module's default internal Modbus/TCP port to 503 by changing holding register 63 = 503. Also, change the default TELNET port to 24 by changing holding regsiter 64 = 24. Fixed a couple of bugs in the Modbus RTU and SY/MAX slave driver so Random Reads work. Must use QUCMTCP.FWL rev 24Jun99 or later. 04Jun99 - First release. No E-net support.